GEOLOGIA GEOTECNICA IDROGEOLOGIA
|
|
- Federigo Ferrario
- 5 anni fa
- Visualizzazioni
Transcript
1 CENTRO STUDI GEOTECNICI SAS SOCIETA DI GEOLOGIA APPLICATA Dott. Geol. Roberto Zago via Cremona n 1/C PADOVA Tel. 049 / Fax 049 / C.F. e P.I. : Numero REA PD GEOLOGIA GEOTECNICA IDROGEOLOGIA COMMITTENTE : VALENTINI VINICIO VALENTINI RENATO PANIZZOLO NADIA INDAGINE GEOGNOSTICA NEL TERRENO DI FONDAZIONE DELLA PROGETTATA DEMOLIZIONE E NUOVA COSTRUZIONE DI UN FABBRICATO AD USO RESIDENZIALE ED ANNESSO RURALE, SITO IN VIA MARINELLE - COMUNE DI DOLO (VENEZIA)) RELAZIONE GEOTECNICA SULL INDAGINE A
2 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica COMMITTENTE : VALENTINI VINICIO VALENTINI RENATO PANIZZOLO NADIA INDAGINE GEOGNOSTICA NEL TERRENO DI FONDAZIONE DELLA PROGETTATA DEMOLIZIONE E NUOVA COSTRUZIONE DI UN FABBRICATO AD USO RESIDENZIALE ED ANNESSO RURALE, SITO IN VIA MARINELLE - COMUNE DI DOLO (VENEZIA) R E L A Z I O N E G E O T E C N I C A 1 - PREMESSA Per Vs. incarico si è provveduto all'esecuzione di un'indagine geotecnica nel terreno di fondazione della progettata demolizione e nuova costruzione di un fabbricato ad uso residenziale ed annesso rurale, sito in via Marinelle n comune di Dolo (Venezia). L'indagine in sito è stata eseguita allo scopo di esaminare la composizione geotecnica del sottosuolo su cui verranno a gravare i carichi di progetto. Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 1 di 16
3 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica In generale è da tener presente che tale tipo di indagine, oltre che consigliabile, è anche prevista dalla normativa nazionale, con particolare riferimento a : D.M. LL.PP. del 11/03/1988 Norme tecniche riguardanti le indagini sui terreni e sulle rocce, la stabilità dei pendii naturali e delle scarpate, i criteri generali e le prescrizioni per la progettazione, l'esecuzione e il collaudo delle opere di sostegno delle terre e delle opere di fondazione. D.M. 16 Gennaio 1996 Norme Tecniche per le costruzioni in zone sismiche Circolare Ministero LL.PP. 10 Aprile 1997 N. 65/AA.GG. Istruzioni per l'applicazione delle Norme Tecniche per le costruzioni in zone sismiche di cui al D.M. 16 Gennaio 1996 Ordinanza P.C.M. n. 3274del Primi elementi in materia di criteri generali per la classificazione sismica del territorio nazionale e di normative tecniche per le costruzioni in zona sismica Norme tecniche per le Costruzioni 2008 Norme tecniche per le costruzioni D.M. 14 gennaio 2008 Eurocodice 7 Progettazione geotecnica Parte 1: Regole generali Eurocodice 8 Indicazioni progettuali per la resistenza sismica delle strutture Parte 5 : Fondazioni, strutture di contenimento ed aspetti geotecnici La modalità di esecuzione delle prove geognostiche nel terreno è stata inoltre uniformata ai suggerimenti contenuti nelle "Raccomandazioni sulla programmazione ed esecuzione delle indagini geotecniche" dell'a.g.i. - Associazione Geotecnica Italiana. Foto postazione Cpt2 Foto postazione Cpt3 Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 2 di 16
4 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica 2 - IMPOSTAZIONE DELL'INDAGINE Nell'area in esame, si è provveduto all esecuzione n 3 prove penetrometriche statiche (denominate Cpt1, Cpt2, Cpt3) ; le prove sono state spinta fino alla profondità di 10.0 m (Cpt1 e Cpt3) e 25.0 m (Cpt2) rispetto al piano d appoggio dello strumento. Si è inoltre provveduto all esecuzione di n 1 sondaggio a carotaggio continuo, spinto fino a 1.4 m di profondità (denominato S1). L'ubicazione dei punti investigati è riportata nella planimetria al termine dell'ultimo capitolo. Come quota zero di partenza delle prove si deve intendere l'attuale piano campagna; tutti i riferimenti di profondità di seguito citati, sono relativi all'inizio prove così definito. Le prove penetrometriche sono state effettuate con un penetrometro statico modello olandese da 10 tonn. di spinta A NORME A.G.I., montato su cingolato. L'indagine penetrometrica consente il rilievo in modo continuo della resistenza a rottura del terreno tramite l'infissione di una punta tipo Begemann; precisamente vengono registrati i seguenti dati: - resistenza alla penetrazione della punta conica o Rp, espressa in kg/cm 2 ; - resistenza all'attrito laterale locale o Rl, espressa in kg/cm 2 ; - resistenza totale alla penetrazione o Rt, espressa in kg. La registrazione delle varie resistenze a rottura del terreno in sito viene effettuata utilizzando una cella idrostatica con quadro di controllo elettronico separato. Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 3 di 16
5 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica 3 - INDAGINE ESEGUITA : RISULTATI Il risultato dell'indagine è contenuto nelle tabelle riportate al termine dell'ultimo capitolo. Si riportano i dati di lettura di campagna ed i valori trasformati, in kg/cm 2, di Rp ed Rl; un apposito diagramma riguarda invece le valutazioni litologiche derivanti sia dal rapporto Rp/Rl, contenuto nelle tabelle, che dal rapporto Schmertmann. Per ogni punto investigato, si riportano inoltre in istogramma, in funzione della profondità, i dati relativi alla resistenza alla punta (Rp) ed alla resistenza all'attrito laterale locale (Rl); per chiarezza grafica non risulta invece diagrammata la resistenza totale (Rt). Al termine delle prove penetrometriche si è provveduto alla misurazione del livello della falda acquifera all'interno dei fori di prova, ottenendo i seguenti risultati: PROFONDITA' FALDA ACQUIFERA Cpt 1 = m Cpt 2 = m Cpt 3 = m Sondaggio S1 = m CARATTERISTICHE DEL TERRENO DI FONDAZIONE Si riporta di seguito una tabella riassuntiva della situazione geotecnica presente nel sottosuolo, con una suddivisione in livelli omogenei; la tabella contiene dati relativi alla natura del terreno, spessore degli strati, resistenza meccanica, coesione, angolo d'attrito. I parametri riguardanti le resistenze caratteristiche del terreno (ovvero coesione non drenata ed angolo d attrito) sono corretti utilizzando gli opportuni coefficienti (indicati nel D.M. 14 Gennaio aggiornato dalla circolare 617 del 2 Febbraio 2009) inseriti all interno delle due tipologie d approccio di calcolo: a) Approccio 1 combinazione 2 b) Approccio 2 Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 4 di 16
6 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica CASO A) - Approccio 1 Combinazione 2 PROFONDITA' LIVELLO (m) 1 da p.c. a 0.60 NATURA GEOTECNICA DEL SOTTOSUOLO terreno agricolo + sottostante limi argilloso di colore marron-nocciola, caratterizzato da resistenza molto bassa VALORE DI RESISTENZA ALLA PUNTA Rp (kg/cm 2 ) VALORE CARATT. MEDIO COESIONE cu k (kg/cm 2 ) VALORE DI PROGETTO MEDIO DI COESIONE cu d (kg/cm 2 ) VALORE CARATT. MEDIO ANGOLO D'ATTR. (φ k ) VALORE DI PROGETTO MEDIO ANGOLO D'ATTR. (φ d ) 2 da 0.60 a limo, limo sabbioso tendente a sabbia limosa nocciola e grigio-nocciola, caratterizzata da bassi valori di resistenza ; tale livello risulta immerso in falda acquifera da a livello a mediocre resistenza, attribuibile a terreni di caratteristiche sabbiose e sabbioso-limose da a Cpt1 e Cpt3 = livello a bassa resistenza, attribuibile a terreni di caratteristiche argillose e argilloso-limose, non rilevato nella Cpt2 dove prosegue il terreno sabbioso a media resistenza da a livello a media e medioelevata resistenza, attribuibile a terreni di caratteristiche sabbiose da a livello a bassa resistenza, attribuibile a terreni di caratteristiche limosoargillose da a livello a medio-elevata resistenza, attribuibile a terreni di caratteristiche sabbiose Per il CASO B) - Approccio 2, i parametri di progetto c ud e φ d non subiscono fattori riduttivi, ovvero sono pari rispettivamente a c uk e φ k. L approccio 1 combinazione 2 (colonna M2) e l approccio 2 (colonna M1) riportati nelle seguente tabella, prevedono infatti i seguenti Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 5 di 16
7 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica coefficienti parziali per correggere i parametri geotecnici caratteristici del terreno ed ottenere i parametri di progetto: Parametro Grandezza alla quale Coefficiente parziale γ M (M1) (M2) applicare il coefficiente parziale Tangente dell angolo di tan φ k γ φ resistenza al taglio Coesione efficace c k γ c Resistenza non drenata c uk γ cu Peso dell unità di γ γ γ volume I parametri di progetto vengo ricavati utilizzando le seguenti equazioni: Cu d = Cu k / γ cu = Cu k / 1.4 ; φ d = arctan (tan(φ k ) / γ φ ) = arctan (tan(φ k ) /1.25) Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 6 di 16
8 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica 4 - CLASSIFICAZIONE DEL SOTTOSUOLO AI FINI SISMICI 4.1 Aspetti locali L area oggetto dell indagine è ubicata nel comune di DOLO (VE) che in base alle normative vigenti nel campo sismico, risulta essere inserito all interno della Zona 4. In base alle indicazioni progettuali fornite la costruzione in esame appartiene agli edifici di Tipo 2 e Classe d Uso II. Le azioni sismiche sulla costruzione vengono valutate in relazione al valore di V R (vita di riferimento) che viene ottenuto moltiplicando la vita nominale V N per il coefficiente d uso C U. Nel caso in esame i parametri V N e C U sono pari rispettivamente a 50 anni e 1.0; in base a tali valori la vita di riferimento V R, che si ricava da V N * C U, è posta uguale a 50. I valori dei parametri sismici caratteristici del sito si ottengono grazie ad un reticolo di punti (distanziati tra loro 5 km) che copre l intero territorio nazionale. Nel caso in esame, si prende come riferimento il punto di coordinate Long. 12,089 e Lat. 45,408 nel calcolo verranno considerati i 4 nodi prossimi a tale punto. Ciascun nodo presenta specifici valori di parametri sismici in funzione di determinati valori, dettati dalla normativa, del tempo di ritorno (T R ). Siti di riferimento Sito 1 ID: Lat: 45,4265 Lon: 12,0668 Distanza: 2677,739 Sito 2 ID: Lat: 45,4273 Lon: 12,1379 Distanza: 4356,406 Sito 3 ID: Lat: 45,3773 Lon: 12,1391 Distanza: 5199,559 Sito 4 ID: Lat: 45,3765 Lon: 12,0681 Distanza: 3895,505 Il valore di T R è funzione del coefficiente P VR, il quale rappresenta la probabilità che l energia generata da un evento sismico colpisca il sito in esame superando le resistenze dell edificio nel periodo di riferimento. Tale probabilità è legata agli stati limite presi in considerazione e risulta essere: Stati Limite PV R : Probabilità di superamento nel periodo di riferimento V R Stati limite di SLO 81% esercizio SLD 63% Stati limite ultimi SLV 10% SLC 5% Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 7 di 16
9 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica T R è pari a : T R = - V R / ln (1-P VR ) Nel caso in esame, essendo V R pari a 50 anni, i valori del tempo di ritorno relativi ai vari stati limite saranno: V R P VR T R (anni) 50 81% (SLO) % (SLD) % (SLV) % (SLC) 975 A tali valori di T R corrispondono i seguenti parametri sismici caratteristici: Sito in esame Parametri sismici latitudine: 45,408 Categoria sottosuolo: C longitudine: 12,089 Periodo di riferimento: 50 anni Vita nominale: 50 Coefficiente cu: 1,0 STATI LIMITE Operatività (SLO): Probabilità di superamento: 81 % Tr: 30 [anni] ag: 0,029 g Fo: 2,492 Tc*: 0,206 [s] Danno (SLD): Probabilità di superamento: 63 % Tr: 50 [anni] ag: 0,035 g Fo: 2,520 Tc*: 0,238 [s] Salvaguardia della vita (SLV): Probabilità di superamento: 10 % Tr: 475 [anni] ag: 0,075 g Fo: 2,637 Tc*: 0,353 [s] Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 8 di 16
10 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica Prevenzione dal collasso (SLC): Probabilità di superamento: 5 % Tr: 975 [anni] ag: 0,095 g Fo: 2,662 Tc*: 0,372 [s] COEFFICIENTI SISMICI stati limite SLO: SLD: SLV: SLC: Ss: 1,500 Cc: 1,770 St: 1,000 Kh: 0,009 Kv: 0,004 Amax: 0,421 Beta: 0,200 Ss: 1,500 Cc: 1,690 St: 1,000 Kh: 0,010 Kv: 0,005 Amax: 0,510 Beta: 0,200 Ss: 1,500 Cc: 1,480 St: 1,000 Kh: 0,022 Kv: 0,011 Amax: 1,099 Beta: 0,200 Ss: 1,500 Cc: 1,460 St: 1,000 Kh: 0,029 Kv: 0,014 Amax: 1,399 Beta: 0, CATEGORIE DI SOTTOSUOLO E CONDIZIONI TOPOGRAFICHE Sulla base della prova penetrometrica Cpt2 eseguita fino alla profondità di circa 25 m, ai fini della valutazione dell azione sismica di progetto, si è notato una moderata prevalenza di terreni appartenenti alla categoria C (valori medi di Vs pari a 264 m/sec). Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 9 di 16
11 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica Tabella categoria sottosuolo Categoria Descrizione V S30 (m/s) A Ammassi rocciosi affioranti o terreni molto rigidi caratterizzati da valori di V S30 superiori a 800 m/s, eventualmente comprendenti in superficie uno strato di alterazione, con spessore massimo pari a 3 m. N SPT30 C u30 (kpa) > S B C D Rocce tenere e depositi di terreni a grana grossa molto addensati o terreni a grana fina molto consistenti con spessori superiori a 30 m, caratterizzati da un graduale miglioramento delle proprietà meccaniche con la profondità. Depositi di terreni a grana grossa mediamente addensati o terreni a grana fina mediamente consistenti con spessori superiori a 30 m, caratterizzati da un graduale miglioramento delle proprietà meccaniche con la profondità. Depositi di terreni a grana grossa scarsamente addensati o di terreni a grana fina scarsamente consistenti, con spessori superiori a 30 m, caratterizzati da un graduale miglioramento delle proprietà meccaniche con la profondità > 50 > < 180 < 15 < E Terreni dei sottosuoli di tipo C o D per spessore non superiore a 20 m, posti sul substrato di riferimento (con V s > 800 m/s). Come C D S1 S2 Depositi di terreni caratterizzati da valori di V s30 inferiori a 100 m/s, che includono uno strato di almeno 8 m di terreni a grana fina di bassa consistenza, oppure che includono almeno 3 m di torba o di argille altamente organiche. Depositi di terreni suscettibili di liquefazione, di argille sensitive o qualsiasi altra categoria di sottosuolo non classificabile nei tipi precedenti. < (1) (1) (1) Da valutare dopo l esecuzione di studi specifici Dal rilievo di campagna, l area in oggetto è caratterizzata da un andamento pianeggiante della superficie topografica priva di qualsiasi elemento morfologico di rilievo e senza evidenze superficiali della presenza di lineamenti di faglia; la categoria d appartenenza della superficie topografica è T1. Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 10 di 16
12 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica Categoria T1 T2 T3 T4 Caratteristiche della superficie topografica Superficie pianeggiante, pendii e rilievi isolati con inclinazione media i 15 Pendii con inclinazione media i>15 Rilievi con larghezza in cresta molto minore che alla base e inclinazione media 15 i 30 Rilievi con larghezza in cresta molto minore che alla base e inclinazione media i>30 Ne deriva che il fattore di amplificazione topografica S T è posto pari a VERIFICHE ALLA LIQUEFAZIONE I dati ottenuti tramite le prove penetrometriche indicano la presenza di terreni potenzialmente soggetti al fenomeno della liquefazione durante un evento sismico. Tali terreni fanno parte delle categorie limoso-sabbiosa, sabbiosolimosa e sabbiosa; nell ambito delle tre prove Cpt eseguite i terreni con tali caratteristiche sono potenzialmente ad iniziare da circa 1 m di profondità e fino a circa 19 m. L individuazione di queste tipologie di terreno ha reso necessario il calcolo del fattore di sicurezza a liquefazione, mediante la correlazione di Robertson e Write A seguito di tale operazione il fattore di sicurezza (FS L ) ottenuto è risultato essere superiore al valore di 1.25, il che indica una BASSA SUSCETTIBILITA alla liquefazione (vedere seguente tabella). FS L Suscettibilità FS L < 1.00 A: Alta suscettibilità 1.00 <= FS L < 1.25 B: Media suscettibilità FS L >= 1.25 C: Bassa suscettibilità Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 11 di 16
13 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica 5 - VERIFICHE NEI CONFRONTI DEGLI STATI LIMITE ULTIMI STATO LIMITE DI RIFERIMENTO VERIFICATO : SLV L ipotesi progettuale prevede la realizzazione di un fabbricato residenziale, sviluppata su una pianta pressocchè rettangolare di lati pari a circa 25 m x 36 m, imposta su una fondazione a platea collocata alla profondità di circa 0.6 m. Carichi della struttura dati forniti Al momento non vi sono dati progettuali sull entità e distribuzione dei carichi della struttura. Valutazione carico limite I valori di seguito calcolati del carico limite dovranno successivamente essere rapportati, in sede di dimensionamento delle opere di fondazione, con le reali misure e tipo di fondazione utilizzate. E' importante sottolineare che le dimensioni di seguito utilizzate ai fini della verifica del q lim, non costituiscono in alcun modo un progetto di fondazione; la scelta del tipo di fondazione ed il suo dimensionamento dovrà avvenire in sede del calcolo delle strutture, dal parte del Professionista incaricato. Sulla base di quanto rilevato al termine delle prove penetrometriche è stata individuata la presenza di falda acquifera a profondità di circa m; con i dati a disposizione è da ritenere pertanto che lo scavo delle opere di fondazione sia al limite delle condizioni di immersione in falda. Data la variabilità stagionale del livello freatico, si consiglia comunque di verificare la quota del livello statico della falda acquifera prima dell'inizio lavori. Le valutazioni di seguito esposte si basano sull individuazione del valore della resistenza di progetto R d del terreno oltre il quale si manifestano fenomeni di rottura del terreno di fondazione. Il carico limite q lim di una fondazione superficiale può essere definito con riferimento a quel valore massimo del carico per il quale in nessun punto del sottosuolo si raggiunge la condizione di rottura (metodo di Frolich); oppure con riferimento a quel valore del carico, maggiore del precedente, per il quale il fenomeno di rottura si è esteso ad un ampio volume del suolo (metodo di Prandtl e successivi). La condizione di sicurezza risulta soddisfatta quanto: Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 12 di 16
14 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica qlim / E d Fattore di Sicurezza e E d R d dove : E d = tensione o carico di progetto R d = resistenza di progetto Il valore del fattore di sicurezza di riferimento da adottare è funzione dell approccio progettuale scelto (Approccio 1 e Approccio 2). Nel presente caso per le verifiche dei carichi limite, si utilizza il seguente metodo: Stati Limite NTC 2008, Approccio 2 (fattore di sicurezza uguale a 2.3). Qualora successivamente si intenda adottare un altra metodologia di approccio (Approccio 1), dovrà esserne data comunicazione e sarà necessario procedere ad un nuovo calcolo. Per giungere alla definizione di Rd occorre definire il carico limite del terreno con le formule tradizionali della geotecnica (Hansen (1970), Terzaghi (1955), Meyerhof (1963), Vesic (1975), Brinch-Hansen (1970)). Nell ottica di una progettazione basata sul metodo degli stati limite, devono essere utilizzati parametri geotecnici opportunamente interpretati (parametri caratteristici Xk) e parametri opportunamente ridotti (parametri di progetto Xd), ottenuti con una stima cautelativa di un dato parametro, in relazione agli stati limite considerati per il progetto. Il carico limite e la resistenza Rd è determinata in modo analitico, con riferimento al valore caratteristico dei vari parametri geotecnici di resistenza del terreno, divisi per i rispettivi coefficienti parziali ym si seguito riportati (tab. 6.2.II delle Norme tecniche per le costruzioni ) : Parametro Grandezza alla quale Coefficiente parziale γ M (M1) (M2) applicare il coefficiente parziale Tangente dell angolo tan φ k γ φ di resistenza al taglio Coesione efficace c k γ c Resistenza non c uk γ cu drenata Peso dell unità di γ γ γ volume Utilizzando la suddivisione geotecnica del sottosuolo riportata a pagina 5, di seguito si procede al calcolo del carico limite del sottosuolo in esame, utilizzando la formula di Brinch - Hansen 1970 (in condizioni drenate), sollecitato dalla seguente tipologia di fondazione : Fondazione a platea - prof. pari a 0.6 m Dimensioni verificate : 25 m x 36 m Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 13 di 16
15 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica Le dimensioni di larghezza fondazionale sopra indicate sono utilizzate all unico scopo di consentire il calcolo del valore di carico limite (altrimenti non calcolabile) e rappresentano le dimensioni più comunemente utilizzate. Non sono pertanto da interpretare come indirizzi progettuali della struttura fondazionale, compito spettante solo al sig. progettista delle strutture. Di seguito si riporta un esempio dello sviluppo dei cunei di rottura nella sezione della prova Cpt2 e degli strati maggiormente coinvolti. Lo sviluppo dei calcoli carico limite / resistenza di progetto, applicato alle tre prove eseguite, porta a definire valori sostanzialmente simili tra i tre punti verificati Si riporta di seguito uno specchio riassuntivo dei risultati dei calcoli relativi alle tre prove CPT poste in corrispondenza alla prevista struttura ; al termine della relazione si rinvia la consultazione dei rispettivi fogli di calcolo (software Geostru Loadcap) : Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 14 di 16
16 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica Condizioni drenate q lim (kg/cm 2 ) Rd (kg/cm 2 ) Platea 25 m x 36 m Cpt1 Cpt2 Cpt Il calcolo porta a determinare valori di carico limite /Rd relativamente contenuti, in ragione delle scadente caratteristiche dei livelli 1 e 2, posti in diretto contatto con il corpo fondazione o a quote immediatamente sottostanti. Il maggior valore di Rd nel punto Cpt3 è dovuto ad una relativa maggior consistenza dei livelli limosi posti immediatamente al di sotto della prevista fondazione. E necessario ora procedere alla verifica relativa alla compatibilità dei carichi con la previsione di cedimento. VERIFICA PREVISIONE CEDIMENTI Non disponendo allo stato attuale di reali valori di Ed, è possibile solo ricercare la condizione di compatibilità tra valori di sovraccarico trasferiti dalla fondazione al sottosuolo (definibili massimi) e previsione di cedimento. Relativamente alla fondazione a platea ipotizzata impostata a 0.6 m di profondità, si verifica la risposta del sottosuolo (in termini di cedimento) nei confronti di una pressione alla base fondazione pari a 0.40 kg/cmq (inferiore quindi al valore della resistenza di progetto). Dato che il bulbo di carico interessa un significativo volume di terreno al di sotto della quota d appoggio fondazione, ai fini di poter eseguire un confronto di previsione cedimento tra i tre punti di prova, alle prove Cpt1 e Cpt3 sono stati assegnati ulteriori 9 m di strato sabbioso, in analogia a quanto rilevato nella prova Cpt2. Rinviando alla lettura completa dei report di calcolo per le due prove, riportate al termine della relazione, si espongono nella seguente tabella i risultati dei rispettivi calcoli : Tensione di progetto massima (kg/cm 2) Cedimento (cm) Cpt Cpt Cpt Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 15 di 16
17 Demolizione e nuova costruzione edificio residenziale via Marinelle - comune di Dolo (VE) Relazione geotecnica Per il punto Cpt1 la previsione di cedimento è più elevata rispetto agli altri due punti, in ragione della presenza in tale punto di uno strato a resistenza molto bassa tra 8-9 m di profondità (non rilevato negli altri due punti di prova). Come si può osservare dallo schema sopra riportato, la previsione di cedimento primario si attesta su valori coerenti con le caratteristiche geotecniche dei terreni rilevati. Dalla stima dei cedimenti ricavati dall applicazione di carichi sopra indicati e sulla base delle dimensioni di fondazione sopra verificate, si ritiene di indicare che il valore di tensione che la fondazione dovrà trasferire al sottosuolo debba essere inferiore al valore di resistenza di progetto (Rd). Per non eccedere nei confronti dei cedimenti, tale tensione dovrà inoltre essere contenuta nei termini sopra riportati. Padova, Gennaio 2013 Dr. Geol. Roberto Zago Centro Studi Geotecnici Sas - via Cremona 1/C - Padova Pagina 16 di 16
18
19 Centro Studi Geotecnici S.n.c. Geologia Geotecnica Idrogeologia Via S. Prosdocimo, Padova - Tel Certificato: A-1-13 PROVA PENETROMETRICA STATICA CPT 1 LETTURE DI CAMPAGNA / VALORI DI RESISTENZA committente: Sigg.ri Valentini-Panizzolo - data prova : 19/01/ lavoro: - quota inizio : Piano Campagna - località: Dolo - via Marinelle - prof. falda : 0,80 m da quota inizio - resp. cantiere: - assist. cantiere: - data emiss. : 22/01/2013 prf LP LL Rp RL Rp/Rl m - - Kg/cm² Kg/cm² - prf LP LL Rp RL Rp/Rl m - - Kg/cm² Kg/cm² - 0,20 0, ,0 0,13 45,0 5,20 3,6 5,1 36,0 0,40 90,0 0,40 0,7 0,9 7,0 0,20 35,0 5,40 4,1 4,7 41,0 0,87 47,0 0,60 0,9 1,2 9,0 0,60 15,0 5,60 3,6 4,9 36,0 0,73 49,0 0,80 1,2 2,1 12,0 0,87 14,0 5,80 4,2 5,3 42,0 1,27 33,0 1,00 1,0 2,3 10,0 0,67 15,0 6,00 4,3 6,2 43,0 1,27 34,0 1,20 0,6 1,6 6,0 1,27 5,0 6,20 4,5 6,4 45,0 0,93 48,0 1,40 1,9 3,8 19,0 1,07 18,0 6,40 4,6 6,0 46,0 1,00 46,0 1,60 4,9 6,5 49,0 1,20 41,0 6,60 5,1 6,6 51,0 0,93 55,0 1,80 6,3 8,1 63,0 1,87 34,0 6,80 6,6 8,0 66,0 1,27 52,0 2,00 6,0 8,8 60,0 1,80 33,0 7,00 4,9 6,8 49,0 1,13 43,0 2,20 5,1 7,8 51,0 0,80 64,0 7,20 5,4 7,1 54,0 1,07 51,0 2,40 4,5 5,7 45,0 1,67 27,0 7,40 5,8 7,4 58,0 1,73 33,0 2,60 4,9 7,4 49,0 0,87 57,0 7,60 6,2 8,8 62,0 0,73 85,0 2,80 3,9 5,2 39,0 0,73 53,0 7,80 2,2 3,3 22,0 0,67 33,0 3,00 2,7 3,8 27,0 0,60 45,0 8,00 0,5 1,5 5,0 0,40 12,0 3,20 2,2 3,1 22,0 0,93 24,0 8,20 0,4 1,0 4,0 0,47 9,0 3,40 3,8 5,2 38,0 0,47 81,0 8,40 0,7 1,4 7,0 0,47 15,0 3,60 3,9 4,6 39,0 1,47 27,0 8,60 0,9 1,6 9,0 0,47 19,0 3,80 2,1 4,3 21,0 0,47 45,0 8,80 0,9 1,6 9,0 0,47 19,0 4,00 1,6 2,3 16,0 0,40 40,0 9,00 0,9 1,6 9,0 0,60 15,0 4,20 2,3 2,9 23,0 0,47 49,0 9,20 1,2 2,1 12,0 0,53 22,0 4,40 2,3 3,0 23,0 0,67 34,0 9,40 7,3 8,1 73,0 1,53 48,0 4,60 2,6 3,6 26,0 0,60 43,0 9,60 7,9 10,2 79,0 0,67 118,0 4,80 3,1 4,0 31,0 0,53 58,0 9,80 7,8 8,8 78,0 0,93 84,0 5,00 4,5 5,3 45,0 1,00 45,0 10,00 7,1 8,5 71, PENETROMETRO STATICO tipo da 10 t - (con anello allargatore) - - COSTANTE DI TRASFORMAZIONE Ct = Velocità Avanzamento punta 2 cm/s - punta meccanica tipo Begemann ø = 35.7 mm (area punta 10 cm² - apertura 60 ) - manicotto laterale (superficie 150 cm²) Software by: Dr.D.Merlin /840820
20 Centro Studi Geotecnici S.n.c. Geologia Geotecnica Idrogeologia Via S. Prosdocimo, Padova - Tel Certificato: A-1-13 PROVA PENETROMETRICA STATICA CPT 2 LETTURE DI CAMPAGNA / VALORI DI RESISTENZA committente: Sigg.ri Valentini-Panizzolo - data prova : 19/01/ lavoro: - quota inizio : Piano Campagna - località: Dolo - via Marinelle - prof. falda : 0,89 m da quota inizio - resp. cantiere: - assist. cantiere: - data emiss. : 22/01/2013 prf LP LL Rp RL Rp/Rl m - - Kg/cm² Kg/cm² - prf LP LL Rp RL Rp/Rl m - - Kg/cm² Kg/cm² - 0,20 0, ,0 0,07 60,0 10,20 6,3 7,6 63,0 1,20 53,0 0,40 0,4 0,5 4,0 0,27 15,0 10,40 6,6 8,4 66,0 1,27 52,0 0,60 0,4 0,8 4,0 0,40 10,0 10,60 7,5 9,4 75,0 1,40 54,0 0,80 1,3 1,9 13,0 0,60 22,0 10,80 5,8 7,9 58,0 1,20 48,0 1,00 1,0 1,9 10,0 0,87 12,0 11,00 4,3 6,1 43,0 1,33 32,0 1,20 0,8 2,1 8,0 0,67 12,0 11,20 2,8 4,8 28,0 1,47 19,0 1,40 1,6 2,6 16,0 0,47 34,0 11,40 7,9 10,1 79,0 1,93 41,0 1,60 3,1 3,8 31,0 0,87 36,0 11,60 5,4 8,3 54,0 1,07 51,0 1,80 3,8 5,1 38,0 0,80 47,0 11,80 8,8 10,4 88,0 2,20 40,0 2,00 5,1 6,3 51,0 0,93 55,0 12,00 6,2 9,5 62,0 1,20 52,0 2,20 4,8 6,2 48,0 1,07 45,0 12,20 12,9 14,7 129,0 2,40 54,0 2,40 4,5 6,1 45,0 1,27 36,0 12,40 7,0 10,6 70,0 1,47 48,0 2,60 4,9 6,8 49,0 1,07 46,0 12,60 15,0 17,2 150,0 2,13 70,0 2,80 5,2 6,8 52,0 1,33 39,0 12,80 8,8 12,0 88,0 1,80 49,0 3,00 4,5 6,5 45,0 0,67 67,0 13,00 8,9 11,6 89,0 1,00 89,0 3,20 4,9 5,9 49,0 1,00 49,0 13,20 11,2 12,7 112,0 1,67 67,0 3,40 6,3 7,8 63,0 1,47 43,0 13,40 9,5 12,0 95,0 1,33 71,0 3,60 5,2 7,4 52,0 1,27 41,0 13,60 8,0 10,0 80,0 1,33 60,0 3,80 4,3 6,2 43,0 1,07 40,0 13,80 7,8 9,8 78,0 1,73 45,0 4,00 3,8 5,4 38,0 0,53 71,0 14,00 7,2 9,8 72,0 0,40 180,0 4,20 3,4 4,2 34,0 0,67 51,0 14,20 13,8 14,4 138,0 2,33 59,0 4,40 2,8 3,8 28,0 1,13 25,0 14,40 8,5 12,0 85,0 2,00 42,0 4,60 3,1 4,8 31,0 0,80 39,0 14,60 13,0 16,0 130,0 1,47 89,0 4,80 3,0 4,2 30,0 0,60 50,0 14,80 11,6 13,8 116,0 1,93 60,0 5,00 3,3 4,2 33,0 1,07 31,0 15,00 2,9 5,8 29,0 1,80 16,0 5,20 4,0 5,6 40,0 0,80 50,0 15,20 7,6 10,3 76,0 2,27 34,0 5,40 3,7 4,9 37,0 0,93 40,0 15,40 7,8 11,2 78,0 1,33 58,0 5,60 3,8 5,2 38,0 1,07 36,0 15,60 19,0 21,0 190,0 0,73 259,0 5,80 3,5 5,1 35,0 1,07 33,0 15,80 11,3 12,4 113,0 1,60 71,0 6,00 3,2 4,8 32,0 1,33 24,0 16,00 5,6 8,0 56,0 2,80 20,0 6,20 4,3 6,3 43,0 0,87 50,0 16,20 1,8 6,0 18,0 1,27 14,0 6,40 6,0 7,3 60,0 1,07 56,0 16,40 8,7 10,6 87,0 3,53 25,0 6,60 6,1 7,7 61,0 0,93 65,0 16,60 10,3 15,6 103,0 1,67 62,0 6,80 6,9 8,3 69,0 2,20 31,0 16,80 18,0 20,5 180,0 1,80 100,0 7,00 9,0 12,3 90,0 1,20 75,0 17,00 16,3 19,0 163,0 2,40 68,0 7,20 10,3 12,1 103,0 1,73 59,0 17,20 11,9 15,5 119,0 1,27 94,0 7,40 12,6 15,2 126,0 1,60 79,0 17,40 10,7 12,6 107,0 1,60 67,0 7,60 11,0 13,4 110,0 2,07 53,0 17,60 13,0 15,4 130,0 2,00 65,0 7,80 9,3 12,4 93,0 1,40 66,0 17,80 20,0 23,0 200,0 1,33 150,0 8,00 10,0 12,1 100,0 2,53 39,0 18,00 20,5 22,5 205,0 2,00 102,0 8,20 11,0 14,8 110,0 1,53 72,0 18,20 17,0 20,0 170,0 1,87 91,0 8,40 7,4 9,7 74,0 1,07 69,0 18,40 16,0 18,8 160,0 1,33 120,0 8,60 4,4 6,0 44,0 0,87 51,0 18,60 19,0 21,0 190,0 1,33 142,0 8,80 6,4 7,7 64,0 0,67 96,0 18,80 22,0 24,0 220,0 1,13 194,0 9,00 7,2 8,2 72,0 1,27 57,0 19,00 14,5 16,2 145,0 2,53 57,0 9,20 6,2 8,1 62,0 1,27 49,0 19,20 3,0 6,8 30,0 1,60 19,0 9,40 7,1 9,0 71,0 1,07 67,0 19,40 1,9 4,3 19,0 0,93 20,0 9,60 8,6 10,2 86,0 1,53 56,0 19,60 1,6 3,0 16,0 1,00 16,0 9,80 6,7 9,0 67,0 1,07 63,0 19,80 1,8 3,3 18,0 0,80 22,0 10,00 6,6 8,2 66,0 0,87 76,0 20,00 3,2 4,4 32,0 1,33 24,0 - PENETROMETRO STATICO tipo da 10 t - (con anello allargatore) - - COSTANTE DI TRASFORMAZIONE Ct = Velocità Avanzamento punta 2 cm/s - punta meccanica tipo Begemann ø = 35.7 mm (area punta 10 cm² - apertura 60 ) - manicotto laterale (superficie 150 cm²) Software by: Dr.D.Merlin /840820
21 Centro Studi Geotecnici S.n.c. Geologia Geotecnica Idrogeologia Via S. Prosdocimo, Padova - Tel Certificato: A-1-13 PROVA PENETROMETRICA STATICA CPT 2 LETTURE DI CAMPAGNA / VALORI DI RESISTENZA committente: Sigg.ri Valentini-Panizzolo - data prova : 19/01/ lavoro: - quota inizio : Piano Campagna - località: Dolo - via Marinelle - prof. falda : 0,89 m da quota inizio - resp. cantiere: - assist. cantiere: - data emiss. : 22/01/2013 prf LP LL Rp RL Rp/Rl m - - Kg/cm² Kg/cm² - prf LP LL Rp RL Rp/Rl m - - Kg/cm² Kg/cm² - 20,20 2,5 4,5 25,0 1,40 18,0 22,80 8,3 11,4 83,0 1,73 48,0 20,40 3,4 5,5 34,0 1,27 27,0 23,00 8,0 10,6 80,0 2,07 39,0 20,60 2,5 4,4 25,0 1,00 25,0 23,20 7,5 10,6 75,0 2,73 27,0 20,80 2,7 4,2 27,0 1,07 25,0 23,40 2,3 6,4 23,0 1,33 17,0 21,00 1,9 3,5 19,0 0,87 22,0 23,60 9,6 11,6 96,0 2,67 36,0 21,20 1,3 2,6 13,0 0,87 15,0 23,80 13,0 17,0 130,0 1,33 97,0 21,40 1,8 3,1 18,0 1,00 18,0 24,00 18,0 20,0 180,0 2,00 90,0 21,60 3,0 4,5 30,0 2,20 14,0 24,20 11,8 14,8 118,0 1,33 88,0 21,80 1,7 5,0 17,0 2,87 6,0 24,40 7,8 9,8 78,0 1,67 47,0 22,00 12,6 16,9 126,0 1,20 105,0 24,60 7,4 9,9 74,0 0,60 123,0 22,20 13,8 15,6 138,0 2,20 63,0 24,80 7,6 8,5 76,0 1,00 76,0 22,40 9,3 12,6 93,0 2,27 41,0 25,00 6,3 7,8 63, ,60 10,0 13,4 100,0 2,07 48,0 - PENETROMETRO STATICO tipo da 10 t - (con anello allargatore) - - COSTANTE DI TRASFORMAZIONE Ct = Velocità Avanzamento punta 2 cm/s - punta meccanica tipo Begemann ø = 35.7 mm (area punta 10 cm² - apertura 60 ) - manicotto laterale (superficie 150 cm²) Software by: Dr.D.Merlin /840820
22 Centro Studi Geotecnici S.n.c. Geologia Geotecnica Idrogeologia Via S. Prosdocimo, Padova - Tel Certificato: A-1-13 PROVA PENETROMETRICA STATICA CPT 3 LETTURE DI CAMPAGNA / VALORI DI RESISTENZA committente: Sigg.ri Valentini-Panizzolo - data prova : 19/01/ lavoro: - quota inizio : Piano Campagna - località: Dolo - via Marinelle - prof. falda : 0,59 m da quota inizio - resp. cantiere: - assist. cantiere: - data emiss. : 22/01/2013 prf LP LL Rp RL Rp/Rl m - - Kg/cm² Kg/cm² - prf LP LL Rp RL Rp/Rl m - - Kg/cm² Kg/cm² - 0,20 0, ,0 0,13 30,0 5,20 2,9 4,0 29,0 0,53 54,0 0,40 0,2 0,4 2,0 0,20 10,0 5,40 3,6 4,4 36,0 0,60 60,0 0,60 0,3 0,6 3,0 0,53 6,0 5,60 5,5 6,4 55,0 1,07 52,0 0,80 0,8 1,6 8,0 0,60 13,0 5,80 4,3 5,9 43,0 0,73 59,0 1,00 1,3 2,2 13,0 0,80 16,0 6,00 3,7 4,8 37,0 0,80 46,0 1,20 1,7 2,9 17,0 0,73 23,0 6,20 4,1 5,3 41,0 0,67 61,0 1,40 1,1 2,2 11,0 0,67 16,0 6,40 3,0 4,0 30,0 0,60 50,0 1,60 2,9 3,9 29,0 1,20 24,0 6,60 2,9 3,8 29,0 0,60 48,0 1,80 5,6 7,4 56,0 1,00 56,0 6,80 3,9 4,8 39,0 0,87 45,0 2,00 4,5 6,0 45,0 0,93 48,0 7,00 4,9 6,2 49,0 1,27 39,0 2,20 5,4 6,8 54,0 1,13 48,0 7,20 7,9 9,8 79,0 0,87 91,0 2,40 3,7 5,4 37,0 1,73 21,0 7,40 13,5 14,8 135,0 1,67 81,0 2,60 3,2 5,8 32,0 0,73 44,0 7,60 10,4 12,9 104,0 1,40 74,0 2,80 3,3 4,4 33,0 0,80 41,0 7,80 10,0 12,1 100,0 2,00 50,0 3,00 3,6 4,8 36,0 0,60 60,0 8,00 16,0 19,0 160,0 2,00 80,0 3,20 4,4 5,3 44,0 0,53 82,0 8,20 15,0 18,0 150,0 1,87 80,0 3,40 5,6 6,4 56,0 1,20 47,0 8,40 13,4 16,2 134,0 2,00 67,0 3,60 4,2 6,0 42,0 0,47 90,0 8,60 11,6 14,6 116,0 1,60 73,0 3,80 6,2 6,9 62,0 1,00 62,0 8,80 8,3 10,7 83,0 1,47 57,0 4,00 5,2 6,7 52,0 1,27 41,0 9,00 4,8 7,0 48,0 1,60 30,0 4,20 3,7 5,6 37,0 0,73 50,0 9,20 3,2 5,6 32,0 1,20 27,0 4,40 3,2 4,3 32,0 0,47 69,0 9,40 3,8 5,6 38,0 1,47 26,0 4,60 2,9 3,6 29,0 1,20 24,0 9,60 3,5 5,7 35,0 0,80 44,0 4,80 3,8 5,6 38,0 0,80 47,0 9,80 4,1 5,3 41,0 1,27 32,0 5,00 2,6 3,8 26,0 0,73 35,0 10,00 5,2 7,1 52, PENETROMETRO STATICO tipo da 10 t - (con anello allargatore) - - COSTANTE DI TRASFORMAZIONE Ct = Velocità Avanzamento punta 2 cm/s - punta meccanica tipo Begemann ø = 35.7 mm (area punta 10 cm² - apertura 60 ) - manicotto laterale (superficie 150 cm²) Software by: Dr.D.Merlin /840820
23 Centro Studi Geotecnici S.n.c. Geologia Geotecnica Idrogeologia Via S. Prosdocimo, Padova - Tel Certificato: A-1-13 PROVA PENETROMETRICA STATICA CPT 1 DIAGRAMMA DI RESISTENZA committente: Sigg.ri Valentini-Panizzolo - data prova : 19/01/ lavoro: - quota inizio : Piano Campagna - località: Dolo - via Marinelle - prof. falda : 0,80 m da quota inizio - resp. cantiere: - scala vert.: 1 : assist. cantiere: - data emiss. : 22/01/2013 Rp (kg/cm²) RL (kg/cm²) 0, ,0 2,0 4,0 6,0 falda m 0,0 m 0,80 1,0 1,0 2,0 2,0 3,0 3,0 4,0 4,0 5,0 5,0 6,0 6,0 7,0 7,0 8,0 8,0 9,0 9,0 10,0 10,0 11,0 11,0 12,0 12,0 13,0 13,0 14,0 14,0 15,0 15,0 16,0 16,0 17,0 17,0 18,0 18,0 19,0 19,0 20,0 20,0 21,0 21,0 22,0 22,0 23,0 23,0 24,0 24,0 25,0 25,0 26,0 26,0 27,0 27,0 28,0 28,0 29,0 29,0 30,0 30, ,0 2,0 4,0 6,0 Software by: Dr.D.Merlin /840820
24 Centro Studi Geotecnici S.n.c. Geologia Geotecnica Idrogeologia Via S. Prosdocimo, Padova - Tel Certificato: A-1-13 PROVA PENETROMETRICA STATICA CPT 2 DIAGRAMMA DI RESISTENZA committente: Sigg.ri Valentini-Panizzolo - data prova : 19/01/ lavoro: - quota inizio : Piano Campagna - località: Dolo - via Marinelle - prof. falda : 0,89 m da quota inizio - resp. cantiere: - scala vert.: 1 : assist. cantiere: - data emiss. : 22/01/2013 Rp (kg/cm²) RL (kg/cm²) 0, ,0 2,0 4,0 6,0 0,0 m falda m 0,89 1,0 1,0 2,0 2,0 3,0 3,0 4,0 4,0 5,0 5,0 6,0 6,0 7,0 7,0 8,0 8,0 9,0 9,0 10,0 10,0 11,0 11,0 12,0 12,0 13,0 13,0 14,0 14,0 15,0 15,0 16,0 16,0 17,0 17,0 18,0 18,0 19,0 19,0 20,0 20,0 21,0 21,0 22,0 22,0 23,0 23,0 24,0 24,0 25,0 25,0 26,0 26,0 27,0 27,0 28,0 28,0 29,0 29,0 30,0 30, ,0 2,0 4,0 6,0 Software by: Dr.D.Merlin /840820
25 Centro Studi Geotecnici S.n.c. Geologia Geotecnica Idrogeologia Via S. Prosdocimo, Padova - Tel Certificato: A-1-13 PROVA PENETROMETRICA STATICA CPT 3 DIAGRAMMA DI RESISTENZA committente: Sigg.ri Valentini-Panizzolo - data prova : 19/01/ lavoro: - quota inizio : Piano Campagna - località: Dolo - via Marinelle - prof. falda : 0,59 m da quota inizio - resp. cantiere: - scala vert.: 1 : assist. cantiere: - data emiss. : 22/01/2013 Rp (kg/cm²) RL (kg/cm²) 0, falda 0,0 2,0 4,0 6,0 0,0 m 0,59 m 1,0 1,0 2,0 2,0 3,0 3,0 4,0 4,0 5,0 5,0 6,0 6,0 7,0 7,0 8,0 8,0 9,0 9,0 10,0 10,0 11,0 11,0 12,0 12,0 13,0 13,0 14,0 14,0 15,0 15,0 16,0 16,0 17,0 17,0 18,0 18,0 19,0 19,0 20,0 20,0 21,0 21,0 22,0 22,0 23,0 23,0 24,0 24,0 25,0 25,0 26,0 26,0 27,0 27,0 28,0 28,0 29,0 29,0 30,0 30, ,0 2,0 4,0 6,0 Software by: Dr.D.Merlin /840820
26 Centro Studi Geotecnici S.n.c. Geologia Geotecnica Idrogeologia Via S. Prosdocimo, Padova - Tel Certificato: A-1-13 PROVA PENETROMETRICA STATICA CPT 1 TABELLA PARAMETRI GEOTECNICI committente: Sigg.ri Valentini-Panizzolo - data prova : 19/01/ lavoro: - quota inizio : Piano Campagna - località: Dolo - via Marinelle - prof. falda : 0,80 m da quota inizio - resp. cantiere: - assist. cantiere: - data emiss. : 22/01/2013 NATURA COESIVA NATURA GRANULARE Prof. Rp Rp/Rl Natura Y' p'vo Cu OCR Eu50 Eu25 Mo Dr ø1s ø2s ø3s ø4s ødm ømy Amax/g E'50 E'25 Mo m kg/cm² (-) Litol. t/m³ kg/cm² kg/cm² (-) kg/cm² kg/cm² % ( ) ( ) ( ) ( ) ( ) ( ) (-) kg/cm² kg/cm² 0, /:/: 1,85 0,04 0,30 85, , , /:/: 1,85 0,07 0,35 43, , , //// 1,85 0,11 0,45 36, , //// 0,92 0,13 0,57 40, , //// 0,90 0,15 0,50 28, , *** 0,46 0,16 0,30 14, , //// 0,99 0,18 0,78 40, , :::: 0,92 0, , , :::: 0,94 0, , , :::: 0,93 0, , , :::: 0,92 0, , , /:/: 1,00 0,27 1,50 53, , , :::: 0,92 0, , , :::: 0,90 0, , , :::: 0,87 0, , , /:/: 0,93 0,34 0,85 19, , , :::: 0,90 0, , , /:/: 1,00 0,38 1,30 29, , , :::: 0,85 0, , , /:/: 0,90 0,42 0,70 11, , , :::: 0,86 0, , , :::: 0,86 0, , , :::: 0,87 0, , , :::: 0,88 0, , , :::: 0,91 0, , , :::: 0,89 0, , , :::: 0,90 0, , , :::: 0,89 0, , , :::: 0,90 0, , , :::: 0,91 0, , , :::: 0,91 0, , , :::: 0,91 0, , , :::: 0,92 0, , , :::: 0,94 0, , , :::: 0,92 0, , , :::: 0,92 0, , , :::: 0,93 0, , , :::: 0,94 0, , , :::: 0,86 0, , , *** 0,46 0,77 0,25 1, , *** 0,46 0,78 0,20 1, , *** 0,46 0,79 0,35 2, , //// 0,88 0,80 0,45 3, , //// 0,88 0,82 0,45 3, , //// 0,88 0,84 0,45 2, , //// 0,92 0,86 0,57 3, , :::: 0,96 0, , , :::: 0,97 0, , , :::: 0,96 0, , , :::: 0,95 0, , Software by: Dr.D.Merlin /840820
27 Centro Studi Geotecnici S.n.c. Geologia Geotecnica Idrogeologia Via S. Prosdocimo, Padova - Tel Certificato: A-1-13 PROVA PENETROMETRICA STATICA CPT 2 TABELLA PARAMETRI GEOTECNICI committente: Sigg.ri Valentini-Panizzolo - data prova : 19/01/ lavoro: - quota inizio : Piano Campagna - località: Dolo - via Marinelle - prof. falda : 0,89 m da quota inizio - resp. cantiere: - assist. cantiere: - data emiss. : 22/01/2013 NATURA COESIVA NATURA GRANULARE Prof. Rp Rp/Rl Natura Y' p'vo Cu OCR Eu50 Eu25 Mo Dr ø1s ø2s ø3s ø4s ødm ømy Amax/g E'50 E'25 Mo m kg/cm² (-) Litol. t/m³ kg/cm² kg/cm² (-) kg/cm² kg/cm² % ( ) ( ) ( ) ( ) ( ) ( ) (-) kg/cm² kg/cm² 0, /:/: 1,85 0,04 0,20 51, , , *** 1,85 0,07 0,20 21, , *** 1,85 0,11 0,20 13, , //// 1,85 0,15 0,60 36, , //// 0,90 0,17 0,50 24, , //// 0,86 0,18 0,40 16, , /:/: 0,90 0,20 0,70 29, , , :::: 0,88 0, , , :::: 0,90 0, , , :::: 0,92 0, , , :::: 0,91 0, , , :::: 0,91 0, , , :::: 0,92 0, , , :::: 0,92 0, , , :::: 0,91 0, , , :::: 0,92 0, , , :::: 0,94 0, , , :::: 0,92 0, , , :::: 0,91 0, , , :::: 0,90 0, , , :::: 0,89 0, , , /:/: 0,96 0,47 0,97 15, , , :::: 0,88 0, , , :::: 0,88 0, , , :::: 0,88 0, , , :::: 0,90 0, , , :::: 0,89 0, , , :::: 0,90 0, , , :::: 0,89 0, , , /:/: 0,97 0,62 1,07 12, , , :::: 0,91 0, , , :::: 0,93 0, , , :::: 0,94 0, , , :::: 0,95 0, , , :::: 0,98 0, , , :::: 1,00 0, , , :::: 1,04 0, , , :::: 1,02 0, , , :::: 0,99 0, , , :::: 1,00 0, , , :::: 1,02 0, , , :::: 0,96 0, , , :::: 0,91 0, , , :::: 0,94 0, , , :::: 0,95 0, , , :::: 0,94 0, , , :::: 0,95 0, , , :::: 0,98 0, , , :::: 0,95 0, , , :::: 0,94 1, , , :::: 0,94 1, , , :::: 0,94 1, , , :::: 0,96 1, , , :::: 0,93 1, , , :::: 0,91 1, , , /:/: 0,96 1,12 0,97 5, , , :::: 0,97 1, , , :::: 0,92 1, , , :::: 0,98 1, , , :::: 0,94 1, , , :::: 1,04 1, , , :::: 0,95 1, , , :::: 1,08 1, , , :::: 0,98 1, , , :::: 0,98 1, , , :::: 1,02 1, , , :::: 0,99 1, , , :::: 0,97 1, , , :::: 0,96 1, , , :::: 0,95 1, , , :::: 1,06 1, , , :::: 0,98 1, , , :::: 1,05 1, , , :::: 1,02 1, , , /:/: 0,96 1,49 0,98 3, , , :::: 0,96 1, , , :::: 0,96 1, , , :::: 1,14 1, , , :::: 1,02 1, , , /:/: 1,01 1,59 1,87 7, , , //// 0,98 1,61 0,75 2, , /:/: 1,04 1,63 2,90 12, , , :::: 1,00 1, , , :::: 1,12 1, , , :::: 1,09 1, , , :::: 1,03 1, , , :::: 1,01 1, , , :::: 1,05 1, , , :::: 1,15 1, , , :::: 1,15 1, , , :::: 1,11 1, , , :::: 1,09 1, , , :::: 1,14 1, , , :::: 1,15 1, , , :::: 1,07 1, , , /:/: 0,96 1,94 1,00 2, , , //// 0,99 1,96 0,78 2, , //// 0,96 1,98 0,70 1, , //// 0,98 2,00 0,75 1, , /:/: 0,97 2,01 1,07 2, , Software by: Dr.D.Merlin /840820
5. CALCOLO DELL AZIONE SISMICA DI PROGETTO (NORME TECNICHE PER LE COSTRUZIONI D.M. 14 GENNAIO 2008)
5. CALCOLO DELL AZIONE SISMICA DI PROGETTO (NORME TECNICHE PER LE COSTRUZIONI D.M. 14 GENNAIO 2008) L azione sismica di progetto si definisce a partire dalla pericolosità sismica di base del sito d interesse
DettagliGEOPROSPEZIONI di Salvetti Andrea e Turrini Giuseppe s.n.c. via Cardinale Maffi, Pisa - tel/fax 050/ PROVE PENETROMETRICHE STATICHE
GEOPROSPEZIONI via Cardinale Maffi, 5 56127 Pisa - tel/fax 050/552430 PROVE PENETROMETRICHE STATICHE CPT 1-2 Elaborati numerici e grafici Data prove di campagna: 16/11/2007 Committente: Ing. Stefano Carani
DettagliCOMUNE DI CASTELFIORENTINO Assessorato Urbanistica
COMUNE DI CASTELFIORENTINO Assessorato Urbanistica Giovanni Occhipinti - Sindaco Arch. Michela Brachi - Dirigente del Settore Urbanistica "Studio di fattibilità atto ad approfondire e definire l'analisi
DettagliRELAZIONE GEOLOGICA E GEOTECNICA
CASADIO & CO. studio tecnico associato Via V.Veneto 1/bis 47100 FORLI Tel: 0543 23923 Email: studio@casadioeco.it P.I. 03480110406 RELAZIONE GEOLOGICA E GEOTECNICA APPROFONDIMENTO SUI CEDIMENTI PER ADDENSAMENTO
DettagliCOMUNE DI BARLETTA. Realizzazione di urbanizzazioni primarie nel piano di zona della nuova 167, 2 e 3 triennio.
Indice 1 Premessa... 2 2 Calcolo dell azione sismica... 2 ~ 1 ~ 1 Premessa Il presente documento è finalizzato a illustrare, in accordo con le Nuove Norme Tecniche DM 14 gennaio 2008, l inquadramento sismico
DettagliORDINE DEI GEOLOGI DEL LAZIO
ORDINE DEI GEOLOGI DEL LAZIO CORSO DI AGGIORNAMENTO PROFESSIONALE Roma 26 settembre 2013 CONFRONTI DELLE CATEGORIE DI SOTTOSUOLO FRA LE NTC08 E LE NUOVE FUTURE NTC: CASI APPLICATIVI Geol. Antonio Colombi
DettagliNORMATIVE DI RIFERIMENTO...
SOMMARIO 1. PREMESSA... 1 2. NORMATIVE DI RIFERIMENTO... 2 3. AZIONE SISMICA... 3 3.1. CATEGORIA DI SOTTOSUOLO E CONDIZIONI TOPOGRAFICHE... 3 3.2. SPETTRO DI RISPOSTA ELASTICO IN ACCELERAZIONE DELLE COMPONENTI
DettagliComune di Fano Località Rosciano REALIZZAZIONE IMPIANTO FOTOVOLTAICO DELLA POTENZA DI KWP COLLEGATO ALLA RETE ELETTRICA DI MEDIA TENSIONE
Comune di Fano Località Rosciano REALIZZAZIONE IMPIANTO FOTOVOLTAICO DELLA POTENZA DI 993.6 KWP COLLEGATO ALLA RETE ELETTRICA DI MEDIA TENSIONE Sommario 1 PREMESSA 2 2 GEOLOGIA-STRATIGRAFIA-GEOMORFOLOGIA-IDROGEOLOGIA
DettagliIl tecnico: Geol. CRISTALLO Filippo Maurizio
! " " " "! #$ ""% " &' ( )# * " " +!', " " ", -' '!! " ' ' " " -! #.! / "! " "" ' " ' - "" ' /! )" "# 0!! 1 " " ' /,!! ' " ++ "' " "!" ' / " " " ' " '' "! - #! /, '!' (, + 2 3456,! - ""!/! +! "! / + ",!
DettagliPROVA PENETROMETRICA STATICA CPT 1 LETTURE DI CAMPAGNA / VALORI DI RESISTENZA 3.010496-143
PROVA PENETROMETRICA STATICA CPT 1 LETTURE DI CAMPAGNA / VALORI DI RESISTENZA 3.010496-143 - resp. cantiere: prf LP LL Rp RL Rp/Rl - - Kg/c² Kg/c² - prf LP LL Rp RL Rp/Rl - - Kg/c² Kg/c² - 0,20 ---- ----
DettagliCOMUNE DI PORTOGRUARO
STUDIO DI GEOLOGIA TECNICA geologia geofisica geotecnica idrogeologia DOTT. MARIA LUISA PICCINATO COMUNE DI PORTOGRUARO INDAGINE GEOGNOSTICA DI UN TERRENO SITO IN VIALE VENEZIA RELAZIONE Via Cavallotti
DettagliALLEGATO I - PROVE PENETROMETRICHE STATICHE DIAGRAMMI DI RESISTENZA TABELLE VALORI DI RESISTENZA VALUTAZIONI LITOLOGICHE PARAMETRI GEOTECNICI
ALLEGATO I - PROVE PENETROMETRICHE STATICHE - DIAGRAMMI DI RESISTENZA -- TABELLE VALORI DI RESISTENZA -- VALUTAZIONI LITOLOGICHE -- PARAMETRI GEOTECNICI Dott. Geol. Maurizio Zamboni LEGENDA VALORI DI RESISTENZA
DettagliPiano Strutturale Comunale Analisi degli ambiti di espansione Comune di Fomignana
Piano Strutturale Comunale Analisi degli ambiti di espansione Comune di Fomignana Synthesis s.r.l. Piazza del Popolo civ. 13 int. 5 44034 Copparo Fe Tel. 0532 860546 Fax 0532 385035 www.synthesissrl.com
DettagliFACOLTÀ DI ARCHITETTURA
UNIVERSITÀ DEGLI STUDI DI CATANIA FACOLTÀ DI ARCHITETTURA Corso di Costruzioni in zona sismica A.A. 2007-2008 dott. ing. Marco Muratore Lezione 4: dall equazione del moto allo spettro di risposta elastico
DettagliCOMUNE DI DAVOLI PROVINCIA DI CATANZARO RELAZIONE SULLE FONDAZIONI
COMUNE DI DAVOLI PROVINCIA DI CATANZARO Oggetto PROGETTO ESECUTIVO DI DEMOLIZIONE E RICOSTRUZIONE DELLA DELEGAZIONE COMUNALE, SITA NELLA FRAZIONE MARINA DEL COMUNE DI DAVOLI Tavola Scala S-09 Elaborato
DettagliIndice RELAZIONE GENERALE ILLUSTRATIVA INDAGINI GEOGNOSTICHE MODELLO GEOTECNICO VALORI CARATTERISTICI... 5
Indice RELAZIONE GENERALE ILLUSTRATIVA... 2 Introduzione... 2 1. INDAGINI GEOGNOSTICHE... 3 2. MODELLO GEOTECNICO... 3 3. VALORI CARATTERISTICI... 5 4. ANALISI SISMICA... 7 Parametri sismici... 7 Combinazioni
Dettagli- Classe di Pericolosità Geologica: Classe 2a: Pericolosità Bassa con presenza di terreni scadenti entro i primi 10 m da p.c..
SCHEDA N. 6.6 - Tipologia di previsione urbanistica: Piano di recupero a destinazione residenziale - Parametri Urbanistici: Rapporto di copertura fondiario 0.40 Altezza massima degli edifici 10.00 m Piani
DettagliRelazione geotecnica inerente la realizzazione di un locale spogliatoio
Relazione geotecnica inerente la realizzazione di un locale spogliatoio Zona di intervento: loc. Leccetti Comune di Volterra Committente: Ing, F. Lombardi Progettista: Ing. F. Lombardi DATA: 4 dicembre
Dettagli1. PERICOLOSITA SISMICA.1 2. CRITERI GENERALI PER LA CLASSIFICAZIONE SISMICA DEL TERRITORIO NAZIONALE
Sommario 1. PERICOLOSITA SISMICA...1 2. CRITERI GENERALI PER LA CLASSIFICAZIONE SISMICA DEL TERRITORIO NAZIONALE..3 3. TABELLE DEI PARAMETRI CHE DEFINISCONO L AZIONE SISMICA...6 4. VITA NOMINALE, CLASSE
DettagliPORTO TURISTICO DI ROMA RELAZIONE GEOTECNICA E SISMICA
PORTO TURISTICO DI ROMA PROGETTO DI AMPLIAMENTO PROGETTO DEFINITIVO RELAZIONE GEOTECNICA E SISMICA INDICE 1. GENERALITÀ... 2 2. NORMATIVE DI RIFERIMENTO... 2 3. CARATTERIZZAZIONE GEOTECNICA... 3 3.1 Caratteristiche
Dettagli------------------------------------ 1 PREMESSA A seguito di specifica richiesta da parte del Settore Pianificazione Territoriale del Comune di Ferrara di adeguare alla DGR 2193/2015 gli elaborati geologici
DettagliPROVEPENETROMETRICHESTATICHEEDINAMICHESUPERPESANTI
PROVEPENETROMETRICHESTATICHEEDINAMICHESUPERPESANTI Attestazione n. 1675-6/00 CERTIFICAZIONE ITALIANA DEI SISTEMI DI QUALITA AZIENDALI Cert. n. 9175.MAPP Indagine geognostica in localitä Pescia Variante
DettagliStudio di Geologia MANTOVANI Geol. Marco Serra San Quirico (AN) PROVA PENETROMETRICA DINAMICA N. 1 committente: Comune di Serra De' Conti data apr-87 cantiere: località: Sistemazione muro campo sportivo
DettagliComune di Casarsa della Delizia Valutazione della sicurezza dei complessi scolastici INDICE GENERALE
INDICE GENERALE 1 Introduzione... 3 2 Descrizione del complesso scolastico... 3 3 Normativa di riferimento e riferimenti tecnici... 3 4 Procedure per la valutazione della sicurezza... 4 4.1. Analisi storico-critica...
DettagliREGIONE LIGURIA PROVINCIA DI SAVONA. COMUNE di BOISSANO
REGIONE LIGURIA PROVINCIA DI SAVONA COMUNE di BOISSANO VARIANTE AL PIANO URBANISTICO COMUNALE, PER OPERE DI DEMOLIZIONE CON TRASFERIMENTO DELLA VOLUMETRIA AD ALTRO LOTTO E INCREMENTO DI VOLUME PER LA REALIZZAZIONE
Dettagli- MODELLO GEOLOGICO - MODELLO GEOTECNICO -
REGIONE EMILIA ROMAGNA PROVINCIA DI FERRARA COMUNE DI PORTOMAGGIORE Azienda Agricola FIBRI di NICOLETTI FABRIZIO Via Grillo Braglia civ. 11 Portomaggiore (FE) PROGETTO PER LA REALIZZAZIONE DI FABBRICATI
DettagliCONSORZIO 1 TOSCANA NORD Consorzio di Bonifica Ente di Diritto Pubblico
REGIONE TOSCANA PIANO DI SVILUPPO RURALE 2014/2020 REGOLAMENTO (UE) 1305/2013 Sottomisura 8.3 Sostegno alla prevenzione dei danni arrecati alle foreste da incendi, calamità naturali ed eventi catastrofici
DettagliPERICOLOSITA SISMICA 2 VITA NOMINALE E CLASSE D USO 4 AZIONE SISMICA 5 CATEGORIA DEL SOTTOSUOLO E CONDIZIONI TOPOGRAFICHE 6
INDICE PERICOLOSITA SISMICA 2 VITA NOMINALE E CLASSE D USO 4 AZIONE SISMICA 5 CATEGORIA DEL SOTTOSUOLO E CONDIZIONI TOPOGRAFICHE 6 SPETTRI E PARAMETRI DI STRUTTURA 7 1 PERICOLOSITA SISMICA L azione sismica
DettagliRiduzione del prelievo irriguo dal fiume Piave Realizzazione della riconversione del sistema irriguo nei comuni di Istrana, Paese e Quinto
E-mail info@consorziopiave.it Sito WEB www.consorziopiave.it C.F. 04355020266 SEDE MONTEBELLUNA (TV) 31044 via S. Maria in Colle, 2 Tel 0423 2917 Fax 0423 601446 UNITA' OPERATIVA TREVISO (TV) 31100 via
DettagliGeo Probing - PROVE PENETROMETRICHE STATICHE - RAPPORTO ED ELABORAZIONE DEI VALORI MISURATI DOCUMENTAZIONE FOTOGRAFICA
Geo Probing di Francesco Becattini Telefono cellulare: 347.6434222 Sede: Strada Perugia - Ponte Valleceppi, n 96 06135 Ponte Valleceppi (PG) Telefono e Fax: 075.5928321 e-mail: f.becattini@geoprobing.it
DettagliPiano Strutturale Comunale Analisi degli ambiti di espansione Comune di Fomignana
Piano Strutturale Comunale Analisi degli ambiti di espansione Comune di Fomignana Synthesis s.r.l. Piazza del Popolo civ. 13 int. 5 4434 Copparo Fe Tel. 532 86546 Fax 532 38535 www.synthesissrl.com info@synthesissrl.com
DettagliProvincia Regionale di Ragusa
Provincia Regionale di Ragusa I STRALCIO FUNZIONALE Responsabile Unico Procedimento Dott. Ing. Salvatore Dipasquale Dirigente Pianificazione del Territorio Dott. Ing. Vincenzo Corallo PROGETTO ESECUTIVO
DettagliCOMUNE DI CASORATE PRIMO (PV) PIANO DI LOTTIZZAZIONE TR5 LE PRIMULE RELAZIONE GEOTECNICA
1. PREMESSE La presente relazione geotecnica, commissionata dal geometra Alberto Gallotti per conto della committenza signor Belloni Mario - residente in Via Alessandro Santagostino, 78-27022 - Casorate
DettagliFIGURA 3.10: Dati input e metodi di calcolo adottati.
Dott. Geol. Thomas Veronese via Roma 10 44021 Codigoro (FE) Telfax 0533 13 cell. 335 524030 FIGURA 3.10: Dati input e metodi di calcolo adottati. Comacchio (Fe) 22 Dott. Geol. Thomas Veronese via Roma
DettagliRELAZIONE GEOTECNICA
Comune di Ascoli Piceno Provincia di Ascoli Piceno RELAZIONE GEOTECNICA OGGETTO: COMMITTENTE: PROGETTO PER IL RECUPERO, LA RISTRUTTURAZIONE ED IL RISANAMENTO CONSERVATIVO DI ALCUNI TRATTI DELLA CINTA MURARIA
DettagliInterventi di sistemazione arginale del torrente Stella in Comune di Quarrata a monte di Ponte alla Catena valutazione controlli compattazione argini
Dr.Geol. R.Peruzzi Interventi di sistemazione arginale del torrente Stella in Comune di Quarrata a monte di Ponte alla Catena valutazione controlli compattazione argini Il presente documento riporta i
DettagliCOMUNE DI GENOLA VIA ROMA, GENOLA COSTRUZIONE DEL 11 BLOCCO DI LOCULI NELL AMPLIAMENTO DEL CIMITERO LOTTO 1 CIG: ZDB212CC58
1 Ing. FERRUA Giuseppe ORDINE INGEGNERI della Provincia di Cuneo - Numero d iscrizione: 703 Residenza di lavoro in via Socrate Forni, 32 (12040) Sant Albano Stura (CN) Tel. 0172 670010, tel. 347 3931633,
DettagliDott. Geol. Michele Aureli
Dott. Geol. Michele Aureli REGIONE ABRUZZO PROVINCIA DI L'AQUILA COMUNE DI SAN BENEDETTO DEI MARSI RELAZIONE SISMICA Istituto Comprensivo "Marruvium" REV. DATA COMMITTENTE GEOLOGO 0 22/07/2016 Amministrazione
DettagliRelazione sulla pericolosità sismica del sito
Relazione sulla pericolosità sismica di base del sito interessato dalle costruzioni PROGETTO PER L'ADEGUAMENTO SISMICO DELLA SCUOLA MATERNA "V.Foscolo" Relazione sulla pericolosità sismica del sito f l
DettagliDipartimento dei Vigili del Fuoco del Soccorso Pubblico e della Difesa Civile Direzione Regionale Lombardia Via Ansperto, 4 - Milano (MI)
Dipartimento dei Vigili del Fuoco del Soccorso Pubblico e della Difesa Civile Direzione Regionale Lombardia Via Ansperto, 4 - Milano (MI) APPROFONDIMENTO GEOTECNICO a supporto del progetto preliminare
DettagliANALISI DI COMPATIBILITA SISMICA DI 2 LIVELLO
ANALISI DI COMPATIBILITA SISMICA DI 2 LIVELLO STUDIO GEOLOGICO Depoli dott. Claudio Via Villatico 11 23823 Colico (LC) / 0341-933011 cell. 3482690532 e-mail claudio@claudiodepoli.com COMMITTENTE : COMUNE
DettagliINDICE 1. PREMESSA NORMATIVE DI RIFERIMENTO... 1
VERIFICA DI ASSOGGETTABILITA' EX ART. 20 D.LGS. 152/06 STRALCIO DI INDICE 1. PREMESSA... 1 2. NORMATIVE DI RIFERIMENTO... 1 3. SISMICITA... 3 3.1 CARATTERIZZAZIONE DELLA PERICOLOSITÀ SISMICA... 5 3.2 CALCOLO
DettagliCONSORZIO 1 TOSCANA NORD Consorzio di Bonifica Ente di Diritto Pubblico
REGIONE TOSCANA PIANO DI SVILUPPO RURALE 2014/2020 REGOLAMENTO (UE) 1305/2013 Sottomisura 8.3 Sostegno alla prevenzione dei danni arrecati alle foreste da incendi, calamità naturali ed eventi catastrofici
DettagliSTUDIO TECNICO DI GEOLOGIA DR. STEFANO TAFFONI
1 STUDIO TECNICO DI GEOLOGIA DR. STEFANO TAFFONI COMUNE DI GROTTAMMARE COMMITTENTE : HOTEL JERRY PIANO PARTICOLAREGGIATO AI SENSI DELL ART. 4 comma 7 della L.R. n. 22/09 e DELL ART. 19 della L.R. n.9/2006
DettagliPiano Strutturale Comunale Analisi degli ambiti di espansione Comune di Fomignana
Piano Strutturale Comunale Analisi degli ambiti di espansione Comune di Fomignana Synthesis s.r.l. Piazza del Popolo civ. 13 int. 5 44034 Copparo Fe Tel. 0532 860546 Fax 0532 385035 www.synthesissrl.com
DettagliPROGETTO ESECUTIVO 1 STRALCIO FUNZIONALE
INTERVENTI DI MIGLIORAMENTO DELLA VIABILITA' PROVINCIALE IN AMBITO URBANO REALIZZAZIONE DEL PERCORSO CICLOPEDONALE TRA IL CENTRO STORICO DI CONCORDIA E CAVANELLA LUNGO LA S.P. N.68 PROGETTO ESECUTIVO 1
DettagliRISTRUTTURAZIONE / AMPLIAMENTO DELLA MENSA SCOLASTICA DI VIA LEONARDO DA VINCI ALLEGATI E TAVOLE
STUDIO DI GEOLOGIA Via R. Sanzio, n.3-21049 - Tradate (VA) Tel. e Fax ufficio: 0331-810710 e_mail: geologoparmigiani@gmail.com COMUNE DI ASSAGO Provincia di MILANO RISTRUTTURAZIONE / AMPLIAMENTO DELLA
DettagliSi compone di sue sezioni distinte, rispettivamente identificate come: INQUADRAMENTO SISMICO CARATTERIZZAZIONE DEI MATERIALI DEL SUBSTRATO
1.0 PREMESSA La presente relazione tecnica espone l inquadramento sismico del sito e la caratterizzazione geotecnica del substrato dell area in cui è prevista la realizzazione del Parcheggio A e del Parcheggio
DettagliComune di Scalenghe PIANO REGOLATORE GENERALE COMUNALE. Adeguamento D.G.R. 13/06/2011 n Relazione geologico-tecnica illustrativa
Sulla base di quanto indicato all interno dell ALLEGATO A Indirizzi regionali per la predisposizione degli studi finalizzati alla prevenzione del rischio sismico negli strumenti di pianificazione, per
DettagliRESISTENZA E STABILITA DI PENDII E FRONTI DI SCAVO IN ZONA SISMICA
S O F T W A R E P E R L A P R O G E T T A Z I O N E RESISTENZA E STABILITA DI PENDII E FRONTI DI SCAVO IN ZONA SISMICA Con il software PEFS Ver. 2.0 per la verifica di resistenza e stabilità dei pendii
DettagliRELAZIONE SULLE FONDAZIONI
RELAZIONE SULLE FONDAZIONI Con riferimento alla allegata relazione geologica e geotecnica redatta dal dott. Geol Samuel Sangiorgi per la nuova scuola elementare di Renazzo posta ad una distanza di circa
DettagliPROGETTO DI UN NUOVO ALLEVAMENTO DI GALLINE OVAIOLE PERIZIA GEOLOGICA E GEOTECNICA 1/21/2015
PROVINCIA DI VENEZIA COMUNE DI SAN STINO DI LIVENZA 1/21/2015 PROGETTO DI UN NUOVO ALLEVAMENTO DI GALLINE OVAIOLE ELAB. 05 PERIZIA GEOLOGICA E GEOTECNICA Proponente : C.P.T. Farm Società Agricola S.r.l.
DettagliP.R.U. PROGETTO CASA COMUNALE STATO DI PROGETTO. Città di San Benedetto del Tronto PROGRAMMA RIQUALIFICAZIONE URBANA. "PRU N.
P.R.U. Artt. 5 e 6 della L.R. 16 del 23.02.2005 PROGRAMMA RIQUALIFICAZIONE URBANA "PRU N.6" - Via Toscana Città di San Benedetto del Tronto P R O V I N C I A D I A S C O L I P I C E N O PROGETTO CASA COMUNALE
DettagliDeterminazione Vs30 Profondità di indagine Buona precisione specialmente con analisi congiunte Possibilità di mettere in luce situazioni
Determinazione Vs30 Profondità di indagine Buona precisione specialmente con analisi congiunte Possibilità di mettere in luce situazioni sismostratigrafiche potenzialmente critiche Valutazione della opportunità
DettagliVERIFICA GEOTECNICA DEL TERRENO DI FONDAZIONE IN UN NUOVO POTENZIALE COMPARTO EDIFICATORIO
VERIFICA GEOTECNICA DEL TERRENO DI FONDAZIONE IN UN NUOVO POTENZIALE COMPARTO EDIFICATORIO La verifica geotecnica riguarda i terreni ricadenti all interno di un nuovo potenziale comparto edificatorio,
DettagliPROGETTO DEFINITIVO RELAZIONE GEOTECNICA
1. INDICE 1. INDICE... 1 2. PREMESSE... 2 3. GEOLOGIA... 2 4. SISMICA... 3 5. MODELLO GEOTECNICO... 12 6. CONCLUSIONI... 17 1 2. PREMESSE Costituisce oggetto della presente relazione lo studio geotecnco
DettagliNOTA INTEGRATIVA ALLA RELAZIONE DI FATTIBILITA' GEOLOGICA
GEODINAMICA STUDIO GEOLOGICO ASSOCIATO di Calò J, Checcucci R, Scotti A. COMUNE DI SCANDICCI ------------------------- PIANO UNITARIO ATTUATIVO DELLE PREVISIONI EDILIZIE ALL'INTERNO DELL'AREA DI TRASFORMAZIONE
DettagliBASE SISMICA A RIFRAZIONE ST1P (TAV. 2)
BASE SISMICA A RIFRAZIONE ST1P (TAV. 2) 1. Il sismostrato-1 è caratterizzato da velocità delle onde P di comprese tra 480 m/sec e 540 m/sec; lo spessore di questo sismostrato è variabile: circa 1 m. (scoppio
DettagliCOMUNE DI NAPOLI. Direzione Centrale Servizio Ciclo Integrato delle Acque
COMUNE DI NAPOLI Direzione Centrale Servizio Ciclo Integrato delle Acque INTERVENTI PRIORITARI SUL BACINO AFFERENTE IL COLLETTORE ARENA S. ANTONIO LOTTO E LOCALITA CASE PUNTELLATE PROGETTO ESECUTIVO STRUTTURE
DettagliDefinizione del soil factor
Definizione del soil factor 1 EC8/P1/C3 Accelerazioni e zonazione sismica La pericolosità sismica di un sito viene riassunta nella a gr, reference peak ground acceleration on type A ground. a gr : max
DettagliLe azioni sismiche e la stabilità dei pendii Elementi introduttivi SISMICA 1
Le azioni sismiche e la stabilità dei pendii Elementi introduttivi SISMICA 1 Il sisma ha la capacità di: porre in movimento corpi di frana quiescenti, esaltare l evoluzione di frane attive, rendere instabili
DettagliRegione. Regione Calabria. Comune Comune di Rogliano di (CS) ... PROGETTO ESECUTIVO IMPIANTO MINIEOLICO EX SCUOLA MATERNA "POVERELLA"
POI Energie Rinnovabili e Risparmio Energetico LINEA DI ATTIVITÀ 1.3 INTERVENTI A SOSTEGNO DELLA PRODUZIONE DI ENERGIA DA FONTI RINNOVABILI NELL AMBITO DELL EFFICIENTAMENTO ENERGETICO DEGLI EDIFICI E UTENZE
DettagliOGGETTO: INTEGRAZIONE RELAZIONE GEOTECNICA DI OTTOBRE 2016
GEOPLANET Geologia Applicata, Geotecnica, Idrogeologia,Geologia Ambientale, Pianificazione Territoriale, Percorsi geologico-storico naturalistici Via Edison 18/a; 23875 Osnago (Lc) Via Olgiasca n.8; 23823
DettagliComune di Montechiaro D Acqui
Aztec Informatica s.r.l. * PAC Relazione di calcolo 1 Comune di Montechiaro D Acqui INTERVENTO n 1) Paratia (berlinese) Normative di riferimento - Legge nr. 1086 del 05/11/1971. Norme per la disciplina
DettagliREGIONE LOMBARDIA. COMUNE di SUZZARA PROVINCIA DI MANTOVA. Via BARACCA, 19 - SUZZARA -MN- PIva TIMBRO E FIRMA. Geol.
REGIONE LOMBARDIA COMUNE di SUZZARA PROVINCIA DI MANTOVA AMBITO ATr03 - COMPARTO A COMMITTENTE Y PARCO s.r.l. Via BARACCA, 19 - SUZZARA -MN- PIva 02300030208 OGGETTO ELAB. N. PIAZZALE STOCCAGGIO AUTOVEICOLI
DettagliComune di: Merana. Normative di riferimento. INTERVENTO n 3) - Consolidamento scarpata Con paratia
Comune di: Merana INTERVENTO n 3) - Consolidamento scarpata Con paratia Normative di riferimento - Legge nr. 1086 del 05/11/1971. Norme per la disciplina delle opere in conglomerato cementizio, normale
DettagliSommario Errore. Il segnalibro non è definito.
Sommario 1. PREMESSA... 2 2. NORMATIVA DI RIFERIMENTO... 2 3. INDAGINI GEOGNOSTICHE... 2 3.1. Campagna indagini... 2 3.2. Definizione della stratigrafia e delle proprietà meccaniche dei terreni... 3 3.3.
DettagliCOMUNE di ALBISOLA SUPERIORE
REGIONE LIGURIA PROVINCIA DI SAVONA COMUNE di ALBISOLA SUPERIORE PROGETTO URBANISTICO OPERATIVO DI INIZIATIVA PRIVATA INTERVENTO DI RISTRUTTURAZIONE URBANISTICA, AI SENSI DELL'ART. 3, COMMA 1, LETTERA
DettagliComune di Rovigo Provincia di Rovigo
geologia indagini geognostiche geotecnica idrogeologia geologia applicata ed ambientale miglioramenti fondiari energia ed impianti progettazione impianti elettrici termici civili, industriali, pubblica
DettagliContraente: Progetto: Cliente: Indagine geologica e geognostica per ampliamento capannone uso artigianale in Turate, via San Martino
Contraente: Progetto: Cliente: Indagine geologica e geognostica per ampliamento capannone uso artigianale in Turate, via San Martino Nord Edil N Contratto : N Doc: Foglio Data N Doc. Cliente: 1 di - 0/07/011
Dettagliregistrati nel registrati nel 2010.
registrati nel 2009. registrati nel 2010. nel 2011. registrati nel 2012. Distretti sismici de registrati nel 2014. registrati nel 2013. nel 2015. MI
DettagliNUOVA LOTTIZZAZIONE IN COMUNE DI RONCADE
REGIONE DEL VENETO PROVINCIA DI TREVISO COMUNE DI RONCADE NUOVA LOTTIZZAZIONE IN COMUNE DI RONCADE INDAGINE GEOGNOSTICA RELAZIONE GEOLOGICA E GEOTECNICA COMMITTENTE: BASSETTO RENATO Lovadina di Spresiano,
DettagliREGIONE LAZIO COMUNE DI GRECCIO
STUDIO DI GEOLOGIA DOTT. GEOL. ALVARO TOZZI ROMA 00199 - VIA GIARABUB,13 - TEL. 06-86217983 CELL. 336 772902 RIETI 02045 - SPINACCETO DI GRECCIO - VIA LIMITI SUD - T. 0746-753270 E-mail: alvarotozzi@alice.it
DettagliProgetto definitivo RD.3.4 RELAZIONE GEOTECNICA PALAZZINA UFFICI VERIFICA PORTANZA TERRENO. BRUNDISIUM S.p.A..
COMUNE DI BRINDISI (BR) PROGETTO PER LA REALIZZAZIONE DI UN DEPOSITO COSTIERO DI IDROCARBURI - GASOLIO E BENZINA CON ANNESSO TERMINALE DI CARICO SITO NELL AREA PROSPICIENTE LA BANCHINA COSTA MORENA RIVA
DettagliALCUNE RIFLESSIONI SULL ORDINANZA 3274
n 1/2004 pagg. 26-31 ALCUNE RIFLESSIONI SULL ORDINANZA 3274 Claudio Cherubini (1), Giovanna Vessia (2) (1) Iscritto n 83ES ORG-Puglia; Dipartimento di Ingegneria Civile ed Ambientale, Politecnico di Bari
DettagliL obiettivo è stato quello di verificare la relazione Rd > Ed, come indicato nelle NTC2008 al paragrafo 2.3.
1) PREMESSA La presente relazione viene redatta in supporto al progetto dell ampliamento della scuola secondaria di primo grado Istituto comprensivo Erasmo da Rotterdam sita in Via Giovanni XXIII, 8 a
DettagliImg. 1.1 Tracciato previsto dal PRG pre vigente del Comune di Bologna
PROVINCIA DI BOLOGNA Settore Pianificazione Territoriale e Trasporti Documento: Relazione Geotecnica Studio di fattibilità del III lotto della strada Lungosavena a Bologna Cod.: S10011-SF-GE02-0 Data:
DettagliComune di Cento. Caratterizzazione geologica, geotecnica e sismica dei terreni di fondazione palestra sita in Via Giovannina 76
Comune di Cento Caratterizzazione geologica, geotecnica e sismica dei terreni di fondazione palestra sita in Via Giovannina 76 Relazione geologica Caratterizzazione geotecnica e sismica dei terreni Consulente
DettagliCORSO SU NTC 2008 E APPLICAZIONI CON C.D.S.Win
CORSO SU NTC 2008 E APPLICAZIONI CON C.D.S.Win Ing. Bruno Biondi - Ing. Carlo Brondi PROGRAMMA DEL CORSO Mattina: 1) Analisi sismica delle strutture secondo le nuove norme tecniche delle costruzioni -
DettagliCOMUNI DI CASOLI E SANT EUSANIO DEL SANGRO (Provincia di Chieti) CALCOLI STATICI STRUTTURE IN C.A. - ZONA SISMICA AI SENSI DEL DM 14/01/2008 -
COMUNI DI CASOLI E SANT EUSANIO DEL SANGRO (Provincia di Chieti) CALCOLI STATICI STRUTTURE IN C.A. - ZONA SISMICA AI SENSI DEL DM 14/01/2008 - Oggetto: Lavori di consolidamento ed adeguamento ponte torrente
DettagliCOMUNE DI CONVERSANO AREA LAVORI PUBBLICI - MANUTENZIONI E PATRIMONIO. Progetto Esecutivo
COMUNE DI CONVERSANO AREA LAVORI PUBBLICI - MANUTENZIONI E PATRIMONIO Progetto Esecutivo Ampliamento e valorizzazione del sistema museale MUSeCO di Conversano. Progetto di riqualificazione e adeguamento
DettagliRELAZIONE GEOLOGICA E MODELLO GEOLOGICO
Dr. Paolo Giovagnoli Geologo Comuni di Cividale del Friuli e Buttrio Provincia di Udine RELAZIONE GEOLOGICA E MODELLO GEOLOGICO a supporto del progetto di collaborazione transfrontaliera per il miglioramento
DettagliRELAZIONE GEOLOGICO TECNICA DI FATTIBILITA' E CLASSIFICAZIONE SISMICA DEL SITO
STUDIO GEOLOGICO TECNICO Dott. Geol. Andrea Diegoli PROVINCIA DI FERRARA COMUNE DI PORTOMAGGIORE Località: Portomaggiore RELAZIONE GEOLOGICO TECNICA DI FATTIBILITA' E CLASSIFICAZIONE SISMICA DEL SITO CARATTERIZZAZIONE
DettagliRELAZIONE GEOTECNICA
PAG.1 -A6 - RELAZIONE GEOTECNICA - RELAZIONE GEOTECNICA 1. DESCRIZIONE DELL OPERA E DEGLI INTERVENTI Su incarico della Committenza è stata eseguita un indagine geologica dalla Dr. Geol. Paolo Bosco allegata,
DettagliComune di FOMBIO Provincia di LODI
Comune di FOMBIO Provincia di LODI STUDIO DELLA COMPONENTE GEOLOGICA, IDROGEOLOGICA E SISMICA DEL PIANO DI GOVERNO DEL TERRITORIO: Legge Regionale 11 marzo 2005, n. 12 D.G.R. 22 dicembre 2005, n. 8/1566
DettagliRELAZIONE ILLUSTRATIVA
STUDIO di GEOLOGIA e GEOTECNICA Dott. Geol. Sandro Zeni Corso Piave, 32 06023 Gualdo Tadino PG Tel.Fax 075-9141595 Emali zenisandro@gmail.com RELAZIONE ILLUSTRATIVA MICROZONAZIONE SISMICA DI LIVELLO -2-
DettagliCOMUNE DI BOLOGNA RELAZIONE DI CALCOLO DELLE OPERE STRUTTURALI - CARATTERISTICHE MATERIALI E - GEOTECNICA
COMUNE DI BOLOGNA PROGETTO ESECUTIVO DEL SISTEMA DI LAMINAZIONE DELLE ACQUE METEORICHE E DELLO SPOSTAMENTO DELLA FOGNATURA MISTA E DELLA CANALETTA DELLE LAME NELL AMBITO DELLA REALIZZAZIONE DELL EDIFICIO
DettagliFONDAZIONI SUPERFICIALI
Associazione Italiana Calcestruzzo armato e Precompresso LA PROGETTAZIONE STRUTTURALE SECONDO IL D.M. 14.01.08 08 E CIRCOLARE APPLICATIVA (Catanzaro, 15-16 Aprile 2010) FONDAZIONI SUPERFICIALI g Ordinario
DettagliREGIONE PUGLIA PROVINCIA DI FOGGIA COMUNE DI PESCHICI
REGIONE PUGLIA PROVINCIA DI FOGGIA COMUNE DI PESCHICI Oggetto: Lavori per la realizzazione delle costruzioni derivanti da volumi da demolire e delocalizzare nel P.I.R.T. Baia di Manaccora Stralcio 1 (Blocco
DettagliCOMUNE DI AZZANO DECIMO Provincia di Pordenone
COMUNE DI AZZANO DECIMO Provincia di Pordenone PROGETTO DELLE OPERE DI URBANIZZAZIONE DELLA VARIANTE N.1 AL PIANO REGOLATORE PARTICOLAREGGIATO COMUNALE DI INIZIATIVA PRIVATA AMBITI B0,1, B0,2.1, B0,2.2
DettagliScelta dello spettro di dispersione fra le singole finestre di durata pari a 2s
Scelta dello spettro di dispersione fra le singole finestre di durata pari a 2s MODELLAZIONE DIRETTA PICKING DELLA CURVA DI DISPERSIONE INTERPRETAZIONE CONGIUNTA SONO UTILI MASW E ReMi? Determinazione
Dettagligiovanni bassi, geologo, via donatori di sangue 13, 26029 soncino (cr) tel. e fax 0374 85486, e_mail:
giovanni bassi, geologo, via donatori di sangue 13, 26029 soncino (cr) tel. e fax 0374 85486, e_mail: bassi.geologo@gmail.com ANALISI PROVE STATICHE CON PENETROMETRO MECCANICO [CPT] Committente: Dott.
DettagliSistema / Edificio / Argomento. Elaborato Livello Tipo / S tipo. Data 03/02/2014. Centrale / Impianto: Titolo Elaborato: GR AD 00135
Elaborato Livello Tipo / S tipo RT - Relazioni ETQ-031282 D Sistema / Edificio / Argomento EMR - Edificio immagazzinamento rifiuti solidi radioattivi Rev. Data 03/02/2014 Centrale / Impianto: GR - Sito
DettagliRELAZIONE GEOTECNICA E SULLE FONDAZIONI
RELAZIONE GEOTECNICA E SULLE FONDAZIONI 1 Indice 1. Caratterizzazione geotecnica dei terreni di fondazione...3 2. Criteri di scelta del tipo di fondazione...4 3. Caratterizzazione meccanica...4 4. Descrizione
Dettagli1 PREMESSA 1.1 Lavoro eseguito
1 PREMESSA Il Committente Consorzio di Bonifica dell Ufita intende effettuare i lavori di costruzione di una vasca di accumulo e stazione di sollevamento nell ambito del progetto di adeguamento del comprensorio
DettagliSegrate 1. Risultati delle analisi MASW e ReMi
Segrate 1 Risultati delle analisi MASW e ReMi Autore: Giovanni Rodina Sito: Cascina Boffalora - Segrate Data: 16 gennaio 2016 1 - Dati sperimentali Numero di ricevitori... 24 Numero di campioni temporali...
DettagliAggiornamento dello studio geologico del territorio comunale (D.G.R. 30 Novembre 2011 n IX/2616)
REGIONE LOMBARDIA Provincia di Milano COMUNE DI RHO Aggiornamento dello studio geologico del territorio comunale (D.G.R. 30 Novembre 2011 n IX/2616) ANALISI SISMICA DI SECONDO LIVELLO N. C o m m e s s
DettagliCOMUNE DI FANO DITTA
COMUNE DI FANO DITTA LONDEI ALDO PAOLONI MARIA -RELAZIONE GEOLOGICA- CARATTERIZZAZIONE E MODELLAZIONE GEOLOGICA DEL LOTTO SITO IN VIA FOSSA SANT ORSO A FANO PER LA REALIZZAZIONE DI UN EDIFICIO RESIDENZIALE.
DettagliStudio geologico del territorio comunale
REGIONE LOMBARDIA Provincia di Varese COMUNE DI ALBIZZATE Studio geologico del territorio comunale L.R. n. 12/2005 D.G.R. 28 Maggio 2008 n. 8/7374 D.G.R. 30 Novembre 2011 n. 9/2616 ANALISI SISMICA DI 2
DettagliGEOLOGO DOTT. LORENZO SEDDA VIA C. COLOMBO 1/B/ AREZZO 0575/ /
GEOLOGO DOTT. LORENZO SEDDA VIA C. COLOMBO 1/B/2 52100 AREZZO 0575/906627 339/1443593 GEOLOGO DOTT. LORENZO SEDDA VIA C. COLOMBO 1/B/2 52100 AREZZO 0575/906627 339/1443593 2 GEOLOGO DOTT. LORENZO SEDDA
Dettagli